TOHO ELECTRONICS TTM200 User Manual
Page 105
![background image](/manuals/373640/105/background.png)
48-7009-E
5-35
■ Where the equipment is used as a simplified programmable controller (manual start and event * start)
Setting example where temperature is raised to 100 °C in 1 minute, maintained at 100 °C for 1 minute,
and then lowered to 0 °C in 1 minute
SEt03
KEY
Name
Setting content
Setting value
FU1
Function key 1 function setting
No setting of time for the key held
pressed/timer start/reset
04
SEt7/8
oUt3/4
Name
Setting content
Setting value
o3F
Target connection setting
Timer 1 output
5
o4F
Target connection setting
Timer 2 output
9
SEt14
tIME1
Name
Setting content
Setting value
tMF1
Function setting
Manual-start
2
oNt1
On delay timer
0 minute
00:00
oFt1
Off delay timer
1 minute
00:02
SEt15
tIME2
Name
Setting content
Setting value
tMF2
Function setting
Event 3 start
10
oNt2
On delay timer
2 minutes
00:02
oFt2
Off delay timer
1 minute
00:01
SEt20
bNK
Name
Setting content
Setting value
bnk01
Control setting
SV
bnk02
Ramp time setting
RMP
For the following setting, enter the inputs during the switchover in bANK (bank switching) in SET 4.
* Set bANK to “0.”
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
0
C
0
RMP
Ramp time setting
Setting turned off
0.0
* Set bANK to “1.”
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
100
C
100
RMP
Ramp time setting
To be raised by 100 °C in 1 minute
100.0
* Set bANK to “2.”
SEt04
CNt
Name
Setting content
Setting value
SV
Control setting
0
C
100
RMP
Ramp time setting
To be raised by 100 °C in 1 minute
100.0
* The bank cannot be switched over unless DI is set after the bank setting is complete.
SEt13
dI
Name
Setting content
Setting value
dIF
Function setting
Both DI 1 and DI 2 to be switched over
0011
Wire the equipment upon completion of setting.