Input 1 type setting
■ Input 1 type setting
SEt01
INP1
Setting content
Initial value
1
INP1
Press the MODE key for making a setting effective (including reverse feed).
0
0 to 20
See the input 1 type setting table.
Set the input type of the input 1.
The input 1 is for a multi-input for thermocouple, resistance temperature detector, voltage and current. Set according to the
input being used.
Input 1 type setting table
Setting
No.
Input type
Connection
Measurement/
setting range
Indicator
resolution
Accuracy
0
K thermocouple
TC
-200.0 to +1372.0
1
C / 0.1
C
Either larger ± (0.3 % + 1 digit) or ± 2°C
Note: ± 3°C for - 100.0 to 0.0°C and ± 4°C for
- 200.0 to - 100.0°C
No specification for 400°C or lower for B
thermocouple
1
J thermocouple
TC
-200.0 to +1200.0
1
C / 0.1
C
2
T thermocouple
TC
-200.0 to + 400.0
1
C / 0.1
C
3
E thermocouple
TC
-200.0 to +1000.0
1
C / 0.1
C
4
R thermocouple
TC
-50 to +1768
1
C
5
S thermocouple
TC
-50 to +1768
1
C
6
B thermocouple
TC
0 to +1800
1
C
7
N thermocouple
TC
-200.0 to +1300.0
1
C / 0.1
C
8
U thermocouple
TC
-200.0 to +400.0
1
C / 0.1
C
Either larger ± (0.3 % + 1 digit) or ± 4°C
± 6°C for lower than 0°C
9
L thermocouple
TC
-200.0 to +900.0
1
C / 0.1
C
10
WRe5-26 thermocouple
TC
0 to +2300
1
C
Either larger ± (0.6 % + 1 digit) or ± 4°C
11
PR40-20 thermocouple
TC
0 to +1880
1
C
± 9.4°C
1 digit
No specification on accuracy for lower than
800°C
12
PL II thermocouple
TC
0.0 to +1390.0
1
C / 0.1
C
Either larger ± (0.3 % + 1 digit) or ± 2°C
13
Pt100
RTD
-200.0 to +850.0
1
C / 0.1
C
Either larger ± (0.3 % + 1 digit) or ± 0.9°C
14
JPt100
RTD
-200.0 to +510.0
1
C / 0.1
C
15
0 - 10 mVDC
TC
-19999 to +29999
Display resolution to be
20000 or less
*1
Random
change of
decimal point
position
allowed
±0.5 % ±1 digit of full scale
16
0 - 1 VDC
I/V
±0.3 % ±1 digit of full scale
17
0 - 5 VDC
I/V
18
1 - 5 VDC
I/V
19
0 - 10 VDC
I/V
20
4 - 20 mADC
I/V
*1 The display range of analog input is min. - 19999 digits and max. +29999 digits. The range, however, can be narrowed by
setting the scaling upper limit (FSH 1) and lower limit (FSL 1) settings. See below for the narrowed display range.
• Display of the lower limit side: Up to - 2 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale
• Display of the lower limit side: Up to - 12 % of the full scale
• Display of the upper limit side: Up to + 12 % of the full scale
Full scale is defined as the range from FSL 1 to FSH 1.
The display range for temperature input (setting Nos. of 0 to 12 in the table above) is fixed.