■ Forward/reverse operation setting
SEt04
CNt
Setting content
Initial value
10
dIR
0
Reverse operation
0
1
Forward operation
Set the forward/reverse operation of the primary control.
• Reverse operation (heating control) is a control where the operating amount increases as PV (measurement value) lower
than SV (setting value).
MV
100
0
△
Low
SV
High
• Forward operation (cooling control) is a control where the operating amount increases as PV higher than SV.
MV
100
0
△
Low
SV
High
Note Take care the following when setting the secondary control.
• The secondary control is automatically set to the forward operation when the primary control is set to 0 or the reverse
operation.
• The secondary control is automatically set to the reverse operation when the primary control is set to 1 or the forward
operation.