TOHO ELECTRONICS TTM200 User Manual
Page 187
48-7009-E
6-39
■ Secondary control loop anomaly PV threshold
SEt04
CNt
Setting content
Initial value
47
tS2
Thermocouple/resistance temperature detector input
0.0 to 999.9 (°C)0 to 999 (°C)
0
Voltage/current input
0 to 9999 (digit)
Set the secondary control loop anomaly PV threshold .
The function is to detect an abnormality in the control loop.
When width of tS1 has PV from an SV , a judgment of the loop anomaly acts.
The real judgment in PS2 and LoP2.
For details, see section “Loop abnormality function” on pages 5-38 and 39.
Control loop
anomaly PV
threshold
(TS2)
SV
setting
value
(TS2)
PV
When PV is out of the judgment
domain, the control loop anomaly is
not judged.
PV indicates present temperature.
Temperature threshold is a value
specified by [SV
– TS2].
Judgment
domain
Non-
judgment
domain