Environmental conditions -7, 2 environmental conditions – TOHO ELECTRONICS TTM200 User Manual
Page 238
![background image](/manuals/373640/238/background.png)
48-7009-E
7-7
TTM-204 (9 pcs)
TTM-207 (12 pcs)
TTM-205 and 209 (14 pcs)
Output 1 monitor
Output 2 monitor
Output 3 monitor
Output 4 monitor
Output 5 monitor
Output 6 monitor
Output 7 monitor
RDY lamp
COM lamp
DI 1 monitor
DI 2 monitor
DI 3 monitor
DI 4 monitor
Timer lamp
5)
Operation section
Key switch, 4 pcs (TTM-204) or 8 pcs (TTM-205, 207 and 209)
UP
:
DOWN
:
Function 1
: FUNC 1
Mode
: MODE
Function 2
: FUNC 2
Function 3
: FUNC 3
Function 4
: FUNC 4
Function 5
: FUNC 5
(6) Other functions
The following functions are equipped with. For details, see the operation specification.
1)
Process control
Signals are output for matching the measurement value to the setting
value.
2)
Blind function
Any parameter can be set to non-display.
3)
Priority screen function
Any parameter screen can be displayed in the run mode screen.
(Max. 16 points)
4)
Key assignment function
FUNC keys 1 to 5 can be assigned for designated specifications.
5)
Timer function
Function of simplified timer can be set as listed below.
Setting accuracy: ± (1.5 % + 0.5 second) of setting time
6)
Bank function
A series of parameters for setting can be switched over.
7)
Program run function
A simple program run of eight steps at most is possible.
7.1.2 Environmental conditions
(1) Standard environment conditions
1)
Temperature range
23 ± 10 °C
2)
Humidity range
45 - 75 %RH
3)
Installation gradient
Base plane ± 3 degrees
4)
Vibration condition
0 G
(2) Use environment conditions
1)
Temperature range
0 - 50 °C
2)
Humidity range
20 - 90 %RH (no dew condensation allowed)
3)
Installation gradient
Base plane ± 10 degrees
(3) Storage environment conditions
1)
Temperature range
-20 - +70 °C (no freeze or dew condensation allowed)
2)
Humidity range
5 - 95 %RH (no dew condensation allowed)
(4) Power supply voltage
100 - 240 VAC, 50/60 Hz
(Allowable voltage range: 85 - 110 %)
24 VAC/DC, 50/60 Hz (205,207,209 are under development.)
(Allowable voltage range: 90 - 110 %)
TTM-204