TOHO ELECTRONICS TTM200 User Manual
Page 140

48-7009-E
5-70
5.6 Explanation of the bank automatic switching function
■ Regarding the bank automatic switching function
The bank function can be automatically switched for each temperature. Setting control parameters for
each temperature beforehand enables realization of optimization and an accurate control. As
parameters unrelated to control can also be set similarly to the case of the normal bank function,
application for each temperature is possible for such functions as the timer and event functions.
Note Precaution when using this function together with the program run function
When using this function together with “program run,” the setting is ineffective even when the
bank designation is set using SET 22 “St*bK step* designated bank setting.” All banks are used
with priority when using the bank automatic switching function [SET 23 BAF
1]. Note that a
bank cannot be divided into parts for assigning one of them to, for example, a program run.
(Behavior diagram for explaining the bank automatic switching run)
SV
SLL
①
②
③
④
⑤
④
①
③
Threshold B: PM1 = 140, PM2 = PM3 =
PM4 = PM5 = PM6 = PM7 = SLH
8BANK (All Threshold * Setting
Z
o
n
e
t
h
re
s
h
o
ld
s
e
tt
in
g
Refer
The designated bank is automatically switched
according to the bank automatic switching source.
SV
value
PM7≦ SLL≦ PM1≦ PM2≦ PM3≦ PM4≦ PM5≦ PM6≦ SET 20 M a x . 1 6 p a ra m e te rs Max. 8BANK (Zone threshold = 7) Bank 0 Bank 1 Bank 2 Bank 3 Bank 4 Bank 5 Bank 6 Bank 7 RMP RMP 10 RMP 10 RMP 10 RMP 10 RMP 5 RMP 5 RMP 10 P1 3.0 P1 4.0 P1 4.0 P1 4.0 P1 4.0 P1 2.0 P1 2.0 P1 4.0 I 0 I 20 I 20 I 20 I 20 I 10 I 10 I 20 D 0 D 5 D 5 D 5 D 5 D 2 D 2 D 5 • • • • • • • • • • • • • • • • • • • • • • • • PM* setting value Bank auto-switching source Bank No. SLH 200 C Bank 7 PM7 160 C ⑤150 C Bank 7 PM6 140 C Bank 6 PM5 120 C Bank 5 PM4 90 C ④100 C Bank 4 PM3 60 C ③70 C Bank 3 PM2 40 C Bank 2 PM1 20 C ②35 C Bank 1 SLL 0 C ①10 C Bank 0 PM1 PM2 PM3 PM4 PM5 PM6 PM7 Bank 6 Bank 5 Bank 4 Bank 3 Bank 2 Bank 1 Bank 0 Bank 7 SLH Eight banks at most (threshold 7) can be used; the diagram is an example of all banks used. The bank can automatically be switched for each temperature. The zone threshold* setting < PM 1 to PM The threshold required for automatic switching is set in SET 23 “bank automatic switching function For this function, SET 20 “bank function” must be set beforehand.
setting value
7 > is set in the SV value setting range from SLL to SLH.
setting mode.”