5.5.4 SET 22 program setting

■ Set a pattern (program) of the program run in the SET 22 program setting.

[Setting items]

• Set “number-of-use-steps” of the program.
• Set “bank designation,” “step SV value” and “step time” of each step.
• Set “repetitive start step,” “repetitive end step” and “execution count.”

[Setting flow]

The flowchart below is for “SET 21 program function setting.” Characters indicated in
parentheses are those displayed on a screen.

SET 21 (C/P) operating type
When C/P

1:

SET 22 (PRoG)

Setting the program setting

mode

When the SET 21 (C/P) operating time is C/P

0 (program run

OFF), the SET 22 screen is not displayed.

Setting the number of use steps

Setting range: 1 to 8

Initial value: 8

Repetition of the number of use steps 1 to StEPN
(Repetitively displays up to StEPN.)

SET 22 (St*bK)

Setting the bank designation

Bank setting (St*bK) *5
Steps 1 to 8: Bank designation

SET 22 (SV*)

Setting the step SV value

Step SV (SV*)
Setting the SV value for each step

Setting range: SLL to SLH

Initial value: 0

SET 22 (tIM*)

Setting the step time

Step time (tIM*) *6
Setting the time of a step

SET 22 (StRSt)

Setting the repetitive start step

Repetitive start step

Setting range: StRSt

1 to repetitive end step setting (ENdSt)

Initial value: 1

SET 22 (ENdSt)

Setting repetitive end step

Repetitive end step

Setting range:

Repetitive start step setting (StRSt StRSt) to

number-of-use-steps setting or StEPN
* If StEPN is set, the value set for the number-of-use-steps

setting is

“repetitive end step setting.”

Initial value: StEPN

SET 22 (RUNP)

Setting the execution count

Setting the execution count

Setting range: RUNP

0 to 9999

(When 0: Unlimitedly repeated.)

Initial value: 1

SET 22 returns to the

beginning.

SET 22 (StEPN)

Setting the number of use

steps (StEPN)

Note Some screens do not appear depending on setting values.

This screen is not displayed in constant value run mode (C/P

0).