5.5.4 SET 22 program setting
■ Set a pattern (program) of the program run in the SET 22 program setting.
[Setting items]
• Set “number-of-use-steps” of the program.
• Set “bank designation,” “step SV value” and “step time” of each step.
• Set “repetitive start step,” “repetitive end step” and “execution count.”
[Setting flow]
The flowchart below is for “SET 21 program function setting.” Characters indicated in
parentheses are those displayed on a screen.
SET 21 (C/P) operating type
When C/P
1:
SET 22 (PRoG)
Setting the program setting
mode
When the SET 21 (C/P) operating time is C/P
0 (program run
OFF), the SET 22 screen is not displayed.
Setting the number of use steps
Setting range: 1 to 8
Initial value: 8
Repetition of the number of use steps 1 to StEPN
(Repetitively displays up to StEPN.)
SET 22 (St*bK)
Setting the bank designation
Bank setting (St*bK) *5
Steps 1 to 8: Bank designation
SET 22 (SV*)
Setting the step SV value
Step SV (SV*)
Setting the SV value for each step
Setting range: SLL to SLH
Initial value: 0
SET 22 (tIM*)
Setting the step time
Step time (tIM*) *6
Setting the time of a step
SET 22 (StRSt)
Setting the repetitive start step
Repetitive start step
Setting range: StRSt
1 to repetitive end step setting (ENdSt)
Initial value: 1
SET 22 (ENdSt)
Setting repetitive end step
Repetitive end step
Setting range:
Repetitive start step setting (StRSt StRSt) to
number-of-use-steps setting or StEPN
* If StEPN is set, the value set for the number-of-use-steps
setting is
“repetitive end step setting.”
Initial value: StEPN
SET 22 (RUNP)
Setting the execution count
Setting the execution count
Setting range: RUNP
0 to 9999
(When 0: Unlimitedly repeated.)
Initial value: 1
SET 22 returns to the
beginning.
SET 22 (StEPN)
Setting the number of use
steps (StEPN)
Note Some screens do not appear depending on setting values.
This screen is not displayed in constant value run mode (C/P
0).