Setup loop input menu – Watlow CLS200 User Manual
Page 98
Chapter 4: Setup
CLS200 Series User’s Guide
82
Watlow Anafaze
Doc.# 0600-3050-2000
NOTE!
If the EPROM information does not match
this description, the EPROM probably con-
tains a custom program. Custom programs
may not work as described in this manual. If
that is the case, contact your dealer for more
information about the firmware.
Setup Loop Input Menu
The SETUP LOOP INPUT menu includes parameters
related to the loop input:
•
Input type
•
Input units
•
Input scaling and calibration
•
Input filtering
Table 4.5
Setup Loop Input
1
This parameter is available only for the pulse loop (loop 5 on
CLS204, loop 9 on CLS208, loop 17 on CLS216).
2
These parameters are available only if LINEAR is selected for
INPUT TYPE.
3
These parameter is available only if INPUT TYPE is set to one of
the thermocouple or RTD options.
Parameter
Default Value
INPUT TYPE?
J
LOOP NAME?
01
INPUT UNITS?
°F
INPUT READING OFFSET?
0
° F
REVERSED T/C DETECT?
3
OFF
INPUT PULSE SAMPLE TIME?
1
1
DISP FORMAT?
2
-999 TO 3000
INPUT SCALING HI PV?
2
1000
INPUT SCALING HI RDG?
2
100.0% FS
INPUT SCALING LO PV?
2
0
INPUT SCALING LO RDG?
2
0.0% FS
INPUT FILTER?
3 SCANS
ALARM
SETUP LOOP 01
INPUT ?