Maximum output, Process variable retransmit example: data logging – Watlow CLS200 User Manual

Page 131

background image

CLS200 Series User’s Guide

Chapter 6: Enhanced Features

Doc.# 0600-3050-2000

Watlow Anafaze

115

By adjusting the maximum and minimum inputs, you can
scale the output appropriately. See Figure 6.2.

Figure 6.2 Linear Scaling of Process Variable

for Retransmit

Maximum Output

Enter the output value (0 to 100%) which corresponds to
the maximum input.

The output will never go above the this maximum output
percentage, regardless of how high the process variable
goes.

Selectable values: 0 to 100%

Process Variable Retransmit Example: Data Logging

The CLS200 controls the temperature of a furnace. The
thermocouple in one of the zones is connected to the con-
troller and is used for closed-loop PID control. An analog re-
corder data logging system is also in place, and a recording
of the process temperature is required. The recorder input
is a linear 4 to 20 mA

Î

(dc) signal representing a process

variable range of 0 to 1000˚ F.

0%

100%

Maximum

Output

Minimum

Output

Minimum

Input

Maximum

Input

Output P

ow

er (%)

Input Process Variable

ALARM

02 HEAT RETRANS
MAX OUT%? 100%