Chapter 6: Enhanced Features

Doc.# 0600-3050-2000

Watlow Anafaze

121

Heat Span

Enter the multiplier to apply to the primary loop heat out-
put percentage.

Selectable values: -9999 to +9999.

Cool Span

Enter the multiplier to apply to the primary loop cool out-
put percentage.

Selectable values: -9999 to +9999.

Cascade Control Example: Water Tank

A tank of water has an inner and outer thermocouple. The
outer thermocouple is located in the center of the water.
The inner thermocouple is located near the heating ele-
ment. The desired temperature of the water is 150˚ F,
which is measured at the outer thermocouple. Using cas-
cade control, the outer thermocouple is used on the primary
loop (in this example, loop 1), and the inner thermocouple
is used on the secondary loop (loop 2). The heater is con-
trolled by loop 2 with a setpoint range of 150 to 190˚ F.

Figure 6.5 Application Using Cascade

Control

ALARM

02 CASCADE
HT SPAN? +9999

ALARM

02 CASCADE
CL SPAN? +9999

CLS200

Water

150

°

Power

Controller

Loop 2 PID Output

Heater

Loop 1 Input

Process Variable

Loop 1: Primary Cascade Loop

Loop 2: Secondary Cascade Loop

Loop 2 Input

Process Variable

Outer

Thermocouple

Inner Thermocouple