EIA/TIA-485 Interface

To communicate with more than one CLS200 series con-
troller on a controller network, or to use communication ca-
ble lengths greater than 50 feet (15.2 m) from PC to
controller, you must use EIA/TIA-485 communications.

When using EIA/TIA-485 communications, you must at-
tach an optically isolated EIA/TIA-232 to EIA/TIA-485 con-
verter to the computer.

Figure 2.32 and Figure 2.33 show the recommended system
wiring. To avoid ground loops, use an optically isolated
EIA/TIA-232 to EIA/TIA-485 converter between the com-
puter and the EIA/TIA-485 network.

Figure 2.32 EIA/TIA-485 Wiring

Cable Recommendations

Watlow Anafaze recommends Belden 9843 cable or its

equivalent. This cable includes three 24 AWG (0.2 mm

2

)

shielded, twisted pairs. It should carry signals of up to
19.2k baud with no more than acceptable losses for up to
4,000 feet (1,220 m).

EIA/TIA-485 Network Connections

Walow Anafaze recommends that you use a single daisy
chain configuration rather than spurs. Run a twisted-pair
cable from the host or the converter to the first CLS200,
and from that point run a second cable to the next CLS200,
and so on. (See Figure 2.33.)

If necessary for servicing, instead of connecting each con-
troller directly into the next, install a terminal strip or con-
nector as close as possible to each CLS200, run a
communications cable from one terminal strip to the next
and connect the controllers to the bus with short lengths of
cable.

EIA/TIA-485 Converter

TXA/TDA/TX-

TXB/TDB/TX+

RXA/RDA/RX-

RXB/RDB/RX+

RXA 25

RXB 23

TXA 26

TXB 24

RXA 25

RXB 23

TXA 26

TXB 24

Do not

A
B

A

B

connect

shield to

CLS200

First CLS200

Last CLS200

JU1

JU1