beautypg.com

Wiring the serial dac – Watlow CLS200 User Manual

Page 60

background image

Chapter 2: Installation

CLS200 Series User’s Guide

44

Watlow Anafaze

Doc.# 0600-3050-2000

Figure 2.29 Dual DAC with Voltage Output

Wiring the Serial DAC

The Serial DAC provides a robust analog output signal.
The module converts the proprietary Serial DAC signal
from the controller’s open collector output in conjunction
with the clock signal to an analog current or voltage. See
Figure 2.30 for wiring. The Serial DAC is user-configurable
for voltage or current output through firmware configura-
tion. See Configuring Serial DAC Outputs on page 188.

The Serial DAC optically isolates the controller’s control
output from the load. When a single Serial DAC is used, it
may be powered by the 5V

Î

(dc) found on the TB50, or by

an external supply referenced to the controller's power sup-
ply. When using multiple Serial DACs, the controller can-
not provide sufficient current; use the 5V

Î

(dc) output from

the CLS200 power supply

TB50 or TB18

PID Loop Output

Dual DAC

V

Î

(dc) Load

+
-

+5V

Î

(dc) 1

+5V

Î

(dc) CTRL

1

2

3

4

5

6

DZC CTRL PID Output
+12/24V

Î

(dc) Exter-

nal Power Supply

+V

Î

(dc) Load Conn.

-mA

Î

(dc) Load Conn.

-External Power

Supply/ V

Î

(dc) Load

Conn.

+ -

12 to 24V

Î

(dc) Power Supply