Base setpoint, Minimum setpoint, Maximum setpoint – Watlow CLS200 User Manual
Page 136

Chapter 6: Enhanced Features
CLS200 Series User’s Guide
120
Watlow Anafaze
Doc.# 0600-3050-2000
Base Setpoint
Enter the setpoint that corresponds to 0% (heat and cool)
output from the primary loop (PRIM. LOOP). This value is
expressed in the same engineering units as the secondary
loop’s process variable.
Selectable values: Any value from the secondary loop’s
minimum process variable to its maximum process vari-
able.
Minimum Setpoint
Enter the lowest value of the secondary loop setpoint. This
minimum setpoint overrides any calculation caused by the
primary loop calling for a lower setpoint. This value is ex-
pressed in the same engineering units as the secondary
loop’s process variable.
Selectable values: Any value from the secondary loop’s
minimum process variable to its maximum process vari-
able.
Maximum Setpoint
Enter the highest value of the secondary loop setpoint. This
maximum setpoint overrides any calculation caused by the
primary loop calling for a higher setpoint. This value is ex-
pressed in the same engineering units as the secondary
loop’s process variable.
Selectable values: Any value from the secondary loop’s
minimum process variable to its maximum process vari-
able.
ALARM
02 CASCADE
BASE SP? 25
ALARM
02 CASCADE
MIN SP? 25
ALARM
02 CASCADE
MAX SP? 180