Failed sensor alarms, System alarms – Watlow CLS200 User Manual
Page 182

Chapter 9: Troubleshooting and Reconfiguring
CLS200 Series User’s Guide
166
Watlow Anafaze
Doc.# 0600-3050-2000
Failed Sensor Alarms
When a failed sensor alarm occurs, the controller switches
to the single loop display for the loop with the alarm and
displays an alarm code on the screen. AnaWin or WatView
displays a message on the alarm screen and logs the alarm
in the event log.
Table 9.3
Failed Sensor Alarm Codes
A failed sensor alarm clears once it has been acknowledged
and the sensor is repaired.
System Alarms
If the controller detects a hardware problem, it displays a
message. The message persists until the condition is cor-
rected.
Table 9.4
Hardware Error Messages
Code
Alarm
Description
FS
Failed Sensor
Open thermocouple.
RT
Reversed
Thermocouple
Temperature changed in the opposite direction than expected.
ST
Shorted
Thermocouple
Temperature failed to change as expected.
RO
RTD Open
Positive or negative lead is broken or disconnected.
RS
RTD Shorted
Positive and negative leads are shorted.
Message
Possible Cause
Recommended Action
LOW POWER
Power supply failed.
See
BATTERY DEAD
RAM battery is dead.
See
.
AW
Ambient warning. Ambient tem-
perature exceeds operating lim-
its by less than 5° C (9° F).
See
H/W AMBIENT FAILURE
Ambient temperature exceeds
operating limits by 5° C (9° F).
Reference voltage (5V
Î
[dc])
shorted to common.
Hardware failed due to exces-
sive voltage on inputs.
See
.
H/W GAIN FAILURE
Hardware failed due to exces-
sive voltage on inputs.
See
H/W OFFSET FAILURE
Hardware failed due to exces-
sive voltage on inputs.
See