beautypg.com

Failed sensor alarms, System alarms – Watlow CLS200 User Manual

Page 182

background image

Chapter 9: Troubleshooting and Reconfiguring

CLS200 Series User’s Guide

166

Watlow Anafaze

Doc.# 0600-3050-2000

Failed Sensor Alarms

When a failed sensor alarm occurs, the controller switches
to the single loop display for the loop with the alarm and
displays an alarm code on the screen. AnaWin or WatView
displays a message on the alarm screen and logs the alarm
in the event log.

Table 9.3

Failed Sensor Alarm Codes

A failed sensor alarm clears once it has been acknowledged
and the sensor is repaired.

System Alarms

If the controller detects a hardware problem, it displays a
message. The message persists until the condition is cor-
rected.

Table 9.4

Hardware Error Messages

Code

Alarm

Description

FS

Failed Sensor

Open thermocouple.

RT

Reversed

Thermocouple

Temperature changed in the opposite direction than expected.

ST

Shorted

Thermocouple

Temperature failed to change as expected.

RO

RTD Open

Positive or negative lead is broken or disconnected.

RS

RTD Shorted

Positive and negative leads are shorted.

Message

Possible Cause

Recommended Action

LOW POWER

Power supply failed.

See

Low Power on page 168

.

BATTERY DEAD

RAM battery is dead.

See

Battery Dead on page 168

.

AW

Ambient warning. Ambient tem-

perature exceeds operating lim-

its by less than 5° C (9° F).

See

Ambient Warning on page

168

.

H/W AMBIENT FAILURE

Ambient temperature exceeds

operating limits by 5° C (9° F).
Reference voltage (5V

Î

[dc])

shorted to common.
Hardware failed due to exces-

sive voltage on inputs.

See

H/W Ambient Failure on

page 169

.

H/W GAIN FAILURE

Hardware failed due to exces-

sive voltage on inputs.

See

H/W Gain or Offset Failure

on page 170

.

H/W OFFSET FAILURE

Hardware failed due to exces-

sive voltage on inputs.

See

H/W Gain or Offset Failure

on page 170

.