You can set the input to be active when low or active when
high. When the input selected for OUTPUT OVERRIDE DIG
INPUT
changes to the specified state, all the loop’s outputs
are set to their sensor fail levels.

Startup Alarm Delay

Set a startup delay for process and deviation alarms for all
loops. The controller does not report these alarm conditions
for the specified number of minutes after the controller
powers up. This feature does not delay failed sensor
alarms.

Selectable values: 0 to 60 minutes.

Keyboard Lock Status

Set this parameter to ON to disable the

CHNG SP, MAN/AUTO,

and

RAMP/SOAK keys on the keypad. If the keys are dis-

abled, pressing them has no effect. If you want to use these
functions, turn off the keyboard lock.

Selectable values: ON or OFF.

Power Up Output Status

WARNING!

Do not set the controller to start from memo-

ry if it may be unsafe for your process to have

outputs on upon power-up.

Set the initial power-up state of the control outputs. If you
choose OFF, all loops are initially set to manual mode at 0%
output. If you choose MEMORY, the loops are restored to the
control status and output value prior to powering down.

See In Case of a Power Failure on page 152 for information
about how this feature affects ramp/soak profiles.

ALARM

STARTUP ALARM
DELAY ? 0 MINS

ALARM

KEYBOARD LOCK
STATUS ? OFF