Setup global parameters menu, Ramp/soak time base, Setup ramp/soak profile menu – Watlow CLS200 User Manual
Page 153: Edit ramp/soak profile

CLS200 Series User’s Guide
Chapter 7: Ramp/Soak
Doc.# 0600-3050-2000
Watlow Anafaze
137
Setup Global Parameters Menu
With the Ramp and Soak option an additional menu ap-
pears on the Setup Global Parameters Menu
Ramp/Soak Time Base
The RAMP/SOAK TIME BASE parameter is in the SETUP
GLOBAL PARAMETERS menu.
Use this parameter to set the time base in all your ramp/
soak profiles. When set to HOURS/MINS, the setpoint is up-
dated once every minute. When set to MINS/SECS, the set-
point is updated once every second.
Selectable values: HOURS/MINS (hours/minutes) or
MINS/SECS (minutes/seconds).
Setup Ramp/Soak Profile Menu
The SETUP RAMP/SOAK PROFILE menu is located be-
tween the SETUP LOOP ALARMS and the MANUAL I/O
TEST menus if the ramp/soak option is installed.
Press
YES to set up or edit ramp/soak profiles.
Edit Ramp/Soak Profile
Choose a profile to set up or edit.
Selectable values: A to Q (17 profiles).
ALARM
RAMP/SOAK TIME
BASE? HOURS/MINS
ALARM
SETUP RAMP/SOAK
PROFILE?
ALARM
EDIT RAMP & SOAK
PROFILE? A