Jumpers in eia/tia-232 connectors – Watlow CLS200 User Manual
Page 62

Chapter 2: Installation
CLS200 Series User’s Guide
46
Watlow Anafaze
Doc.# 0600-3050-2000
Table 2.8
EIA/TIA-232 Connections
Jumpers in EIA/TIA-232 Connectors
Some software programs and some operator interface ter-
minals require a Clear to Send (CTS) signal in response to
their Request to Send (RTS) signal, or a Data Set Ready
(DSR) in response to their Data Terminal Ready (DTR).
The CLS200 is not configured to receive or transmit these
signals. To use such software with the CLS200, jumper the
RTS to the CTS and the DTR to the DSR in the DB connec-
tor. Table 2.9 lists the standard pin assignments for DB-9
and DB-25 connectors.
Table 2.9
RTS/CTS Pins in DB-9 and DB-25
Connectors
Cables manufactured by Watlow Anafaze for EIA/TIA-232
communications include these jumpers. Neither AnaWin
nor Anasoft software requires these jumpers.
Figure 2.31 Connecting One CLS200 to a Com-
puter Using EIA/TIA-232
Wire
Color
CLS200
TB1
DB 9
Connector
DB 25
Connector
White
TX Pin 26
RX Pin 2
RX Pin 3
Red
RX Pin 25
TX Pin 3
TX Pin 2
Black
GND Pin 23
GND Pin 5
GND Pin 7
Green
GND Pin 24
N/U Pin 9
N/U Pin 22
Shield
N/C
GND Pin 5
GND Pin 7
DB-9
DB-25
RTS
7
4
CTS
8
5
DTR
4
20
DSR
6
6
WA
TLO
W ANAF
AZE CLS200
WA
TLO
W ANAF
AZE CLS200
LOOP
LOOP
PR
OCESS
PR
OCESS
UNITS
UNITS
ALARM
ALARM
SETPOINT
SETPOINT
ST
ATUS
ST
ATUS
OUT%
OUT%
MAN
AU
TO
MAN
AU
TO
CHNG
SP
CHNG
SP
A
LA
RM
A
CK
ALARM
A
CK
RAMP
SO
AK
RAMP
SO
AK
YES
YES
N
O
NO
BA
CK
BA
CK
EN
TER
ENTER
EIA/TIA-232
cable