Chapter 9: Troubleshooting and Reconfiguring

CLS200 Series User’s Guide

182

Watlow Anafaze

Doc.# 0600-3050-2000

CLS204 and CLS208 Voltage Inputs

For each voltage input on a CLS204 and CLS208 controller
you must install two resistors. The resistances must be cor-
rect for the expected input range. Note the resistor pack
(RP) locations have three through holes. Install the RD re-
sistor as indicated in the illustration below.

Table 9.8

Resistor Values for CLS204 and

CLS208 Voltage Inputs

Resistor tolerance:

±

0.1%

Table 9.9

Resistor Locations for CLS204 and

CLS208 Voltage Inputs

Resistor Values

Input Range

RC

RD

0 to100mV

Î

(dc)

499

750

0 to 500mV

Î

(dc)

5.49 k

750

0 to 1V

Î

(dc)

6.91 k

442.0

0 to 5V

Î

(dc)

39.2 k

475.0

0 to 10V

Î

(dc)

49.9 k

301.0

0 to 12V

Î

(dc)

84.5 k

422.0

Resistor Locations

Loop

RC

RD

1

R58

RP1

2

R56

RP2

3

R54

RP3

4

R52

RP4

5

R50

RP5

6

R48

RP6

7

R46

RP7

8

R44

RP8

RP#

RD