beautypg.com

Job select digital inputs – Watlow CLS200 User Manual

Page 92

background image

Chapter 4: Setup

CLS200 Series User’s Guide

76

Watlow Anafaze

Doc.# 0600-3050-2000

Job Select Digital Inputs

Set the number of job select inputs. The controller uses
these inputs as a binary code that specifies the job number
to run. The number of inputs you choose in this parameter
controls the number of jobs you can select remotely.

If you select NONE, digital inputs do not affect job selection.
Jobs may be loaded and saved using the LOAD SETUP FROM
JOB
and SAVE SETUP TO JOB parameters.

Selectable values: 1, 2 or 3 inputs, or NONE. These choices
have the following effect:

Table 4.2

Job Select Inputs

Table 4.3 shows which input states select which jobs. When
nothing is connected, the inputs are all false and job 1 is se-
lected.

Table 4.3

Job Selected for Various Input

States

Setting

Enables

1

Jobs 1-2

2

Jobs 1-4

3

Jobs 1-8

NONE

Disables remote job selection

Digital Input 3 Digital Input 2 Digital Input 1

Job

No.

F

F

F

1

F

F

T

2

F

T

F

3

F

T

T

4

T

F

F

5

T

F

T

6

T

T

F

7

T

T

T

8

ALARM

JOB SELECT
DIG INPUTS? NONE