Chapter 2: Installation

CLS200 Series User’s Guide

38

Watlow Anafaze

Doc.# 0600-3050-2000

Figure 2.24 Output Connections Using

External Power Supply

CPU Watchdog Timer

The CPU watchdog timer constantly monitors the micro-
processor. It is a sink output located on TB50 terminal 6 or
TB18 terminal 3. The output can be connected to an exter-
nal circuit or device in order to determine if the controller
is powered and operational. Do not exceed 5V

Î

(dc), 10

mA

Î

(dc) rating for the watchdog output. The output is low

(on) when the microprocessor is operating; when it stops
operating, the output goes high (off).

Figure 2.25 and Figure 2.26 show the recommended circuit
for the watchdog timer output for the TB50 and the TB18.

Figure 2.25 TB50 Watchdog Timer Output

Figure 2.26 TB18 Watchdog Timer Output

Digital Inputs

All digital inputs are transistor-transistor logic (TTL) level
inputs referenced to control common and the internal +5V
power supply of the CLS200.

When an input is connected to the controller common, the
input is considered on. Otherwise, the input is considered

Heat Output

Cool Output

Alarm Output

Common

+

-

SSR

TB50 or TB18

- PS +

+

-

SSR

+

-

SSR

SSR

+ 5V

Î

(dc)

Watchdog Timer

(Terminal 1)

(Terminal 6)

TB50

+

-

SSR

+ 5V

Î

(dc)

Watchdog Timer

(Terminal 1)

(Terminal 3)

TB18

+

-