beautypg.com

Heat or cool cycle time, Sdac mode, Sdac low value – Watlow CLS200 User Manual

Page 111: Sdac high value

background image

CLS200 Series User’s Guide

Chapter 4: Setup

Doc.# 0600-3050-2000

Watlow Anafaze

95

Heat or Cool Cycle Time

Set the cycle time for time proportioning outputs.

This parameter appears only if the heat or cool output type
for the loop is set to time proportioning (TP).

Selectable values: 1 to 255 seconds.

SDAC Mode

Select the Serial DAC output signal.

Selectable values: CURRENT or VOLTAGE.

SDAC Low Value

Set the low output signal level for the Serial DAC. The Se-
rial DAC converts 0% output from the controller to the val-
ue set here.

Set the high and low values to match the input range of the
output device. For instance, if the output device has a 0.00-
10.00 V range, set the SDAC LO VALUE to 0.00 VDC and
set the SDAC HI VALUE to 10.00 VDC.

Selectable values: 0.00 to 9.00 VDC or 0.0 to 19.90
MA
. This value must be less than the SDAC HI VALUE.

SDAC High Value

Set the high output signal level for the Serial DAC. The Se-
rial DAC converts 100% output from the controller to the
value set here.

Set the high and low values to match the range of the out-
put device. For instance, if the output device has a 4 to 20

ALARM

01 HEAT OUTPUT
CYCLE TIME? 10S

ALARM

01 SDAC MODE?
VOLTAGE

ALARM

01 SDAC LO VALUE?
0.00 VDC