Heat or cool cycle time, Sdac mode, Sdac low value – Watlow CLS200 User Manual
Page 111: Sdac high value

CLS200 Series User’s Guide
Chapter 4: Setup
Doc.# 0600-3050-2000
Watlow Anafaze
95
Heat or Cool Cycle Time
Set the cycle time for time proportioning outputs.
This parameter appears only if the heat or cool output type
for the loop is set to time proportioning (TP).
Selectable values: 1 to 255 seconds.
SDAC Mode
Select the Serial DAC output signal.
Selectable values: CURRENT or VOLTAGE.
SDAC Low Value
Set the low output signal level for the Serial DAC. The Se-
rial DAC converts 0% output from the controller to the val-
ue set here.
Set the high and low values to match the input range of the
output device. For instance, if the output device has a 0.00-
10.00 V range, set the SDAC LO VALUE to 0.00 VDC and
set the SDAC HI VALUE to 10.00 VDC.
Selectable values: 0.00 to 9.00 VDC or 0.0 to 19.90
MA. This value must be less than the SDAC HI VALUE.
SDAC High Value
Set the high output signal level for the Serial DAC. The Se-
rial DAC converts 100% output from the controller to the
value set here.
Set the high and low values to match the range of the out-
put device. For instance, if the output device has a 4 to 20
ALARM
01 HEAT OUTPUT
CYCLE TIME? 10S
ALARM
01 SDAC MODE?
VOLTAGE
ALARM
01 SDAC LO VALUE?
0.00 VDC