Chapter 7: Ramp/Soak

CLS200 Series User’s Guide

138

Watlow Anafaze

Doc.# 0600-3050-2000

Copy Setup From Profile

Set up similar profiles quickly by copying the setup of an
existing profile.

Selectable values: A to Q.

Tolerance Alarm Time

Set a limit on how long the process variable can be outside
the tolerance set for the segment before the tolerance
alarm occurs.

If the process variable does not return within the tolerance,
the tolerance alarm will recur after the tolerance alarm
time elapses again.

If the alarm persists, you may want to reset the profile.

Selectable values: 0:00 to 99:59 (minutes or hours, de-
pending on the time base setting).

Ready Segment Setpoint

When you assign a profile to a loop, the profile does not
start immediately. Instead, it goes to the ready segment
(segment 0) and stays there until you put the profile in run
mode.

You can set a setpoint, assign events, and set event states
for the ready segment. Use this parameter to set the ready
segment setpoint. Setting the setpoint to OFF ensures that
control outputs for the loop running the profile will not
come on.

Selectable values: -999 to 9999, or OFF. See Setpoints
and Tolerances for Various Input Types on page 144.

ALARM

COPY SETUP
FROM PROFILE ? Q

ALARM

A OUT-OF-TOLRNCE
ALARM TIME? 1:00

ALARM

A READY SEGMENT
SETPOINT? OFF