CLS200 Series User’s Guide

Chapter 6: Enhanced Features

Doc.# 0600-3050-2000

Watlow Anafaze

117

Table 6.1

Application Example: Setting Up

Process Variable Retransmit

Display

User Input

Press

YES.

Enter 01 for loop 1 process variable. Press

ENTER.

Enter the minimum input value, which corresponds to the minimum

output percentage. For a range of 0 to 1000° F, set the minimum

input value to 0° F. Press

ENTER.

Enter the minimum output percentage, from 0 to 100%. For this

example we will assume a full span with a minimum of 0%. Press

ENTER.

Enter the maximum input value, which corresponds to the maxi-

mum output percentage. For a range of 0 to 1000° F, set the maxi-

mum input value to 1000° F. Press

ENTER.

Enter the maximum output percentage, from 0 to 100%. For this

example we will assume a full span with a maximum of 100%.

Press

ENTER.

The process variable retransmit section of the controller program-

ming is now completed. We are not using the cool output of loop 2

to retransmit a process variable, so choose NONE. Press

ENTER.

ALARM

SETUP LOOP 02
PV RETRANSMIT

ALARM

02 HEAT OUTPUT
RETRANS PV? 01

ALARM

02 HEAT RETRANS
MIN INP? 0

ALARM

02 HEAT RETRANS
MIN OUT%? 0

ALARM

02 HEAT RETRANS
MAX INP? 1000

ALARM

02 HEAT RETRANS
MAX OUT%? 100

ALARM

02 COOL OUTPUT
RETRANS PV? NONE