Watlow CLS200 User Manual
Page 133
CLS200 Series User’s Guide
Chapter 6: Enhanced Features
Doc.# 0600-3050-2000
Watlow Anafaze
117
Table 6.1
Application Example: Setting Up
Process Variable Retransmit
Display
User Input
Press
YES.
Enter 01 for loop 1 process variable. Press
ENTER.
Enter the minimum input value, which corresponds to the minimum
output percentage. For a range of 0 to 1000° F, set the minimum
input value to 0° F. Press
ENTER.
Enter the minimum output percentage, from 0 to 100%. For this
example we will assume a full span with a minimum of 0%. Press
ENTER.
Enter the maximum input value, which corresponds to the maxi-
mum output percentage. For a range of 0 to 1000° F, set the maxi-
mum input value to 1000° F. Press
ENTER.
Enter the maximum output percentage, from 0 to 100%. For this
example we will assume a full span with a maximum of 100%.
Press
ENTER.
The process variable retransmit section of the controller program-
ming is now completed. We are not using the cool output of loop 2
to retransmit a process variable, so choose NONE. Press
ENTER.
ALARM
SETUP LOOP 02
PV RETRANSMIT
ALARM
02 HEAT OUTPUT
RETRANS PV? 01
ALARM
02 HEAT RETRANS
MIN INP? 0
ALARM
02 HEAT RETRANS
MIN OUT%? 0
ALARM
02 HEAT RETRANS
MAX INP? 1000
ALARM
02 HEAT RETRANS
MAX OUT%? 100
ALARM
02 COOL OUTPUT
RETRANS PV? NONE