Chapter 5: Extruder Control

CLS200 Series User’s Guide

108

Watlow Anafaze

Doc.# 0600-3050-2000

Figure 5.1 Cool Output Nonlinear Output

Curve

The COOL OUTPUT parameter is located in the SETUP
LOOP OUTPUTS
menu. Select one of three nonlinear or lin-
ear output curves for cooling.

Defaults

The Extruder Control Firmware uses different defaults for
some parameters in the SETUP LOOP CONTROL
PARAMS
menu. Furthermore, a unique set of control de-
faults are asserted whenever the COOL OUTPUT parame-
ter on the SETUP LOOP OUTPUTS menu is changed.
Table 5.1 through Table 5.3 on page 109 list the default pa-
rameter settings for each cool output curve.

NOTE!

Changing the cool output curve parameter

will change control parameter settings to de-

faults for that particular cool output curve.

Calculated by PID

Output

0

0

3

2

4

7

12

19

29

44

66

8

13

19

27

36

48

62

79

10

20

40

60

80

100

30

50

70

90

20

40

60

80

100

Oil

Fan

H2O