Tb50 connections – Watlow CLS200 User Manual
Page 57

CLS200 Series User’s Guide
Chapter 2: Installation
Doc.# 0600-3050-2000
Watlow Anafaze
41
TB50 Connections
Table 2.6
TB50 Connections for CLS204 and
CLS208
1
The indicated outputs are dedicated for control when enabled in
the loop setup. If one or both of a loop’s outputs are disabled, the
corresponding digital outputs become available for alarms or
ramp/soak events.
2
If you install a Watlow Anafaze Serial DAC, the controller uses
digital output 34 (terminal 10) for a clock line. You cannot use out-
put 34 for anything else when you have a Serial DAC installed.
Control Output
1
Control Output
1
Ter-
minal
Function
CLS208
CLS204
Ter-
minal
Function
CLS208 CLS204
1
+5V
Î
(dc)
2
+5V
Î
(dc)
3
CTRL COM
4
CTRL COM
5
Not Used
6
Watchdog
Timer
7
Pulse Input
8
Global Alarm
9
Output 1
Loop 1 heat
Loop 1 heat
10
Output 34
2
11
Output 2
Loop 2 heat
Loop 2 heat
12
Output 33
13
Output 3
Loop 3 heat
Loop 3 heat
14
Output 32
15
Output 4
Loop 4 heat
Loop 4 heat
16
Output 31
17
Output 5
Loop 5 heat
Pulse loop heat
18
Output 30
19
Output 6
Loop 6 heat
Loop 1 cool
20
Output 29
21
Output 7
Loop 7 heat
Loop 2 cool
22
Output 28
23
Output 8
Loop 8 heat
Loop 3 cool
24
Output 27
25
Output 9
Pulse loop
heat
Loop 4 cool
26
Output 26
27
Output 10
Loop 1 cool
Pulse loop cool
28
Output 25
29
Output 11
Loop 2 cool
30
Output 24
31
Output 12
Loop 3 cool
32
Output 23
33
Output 13
Loop 4 cool
34
Output 22
35
Output 14
Loop 5 cool
36
Output 21
37
Output 15
Loop 6 cool
38
Output 20
39
Output 16
Loop 7 cool
40
Output 19
41
Output 17
Loop 8 cool
42
Output 18
Pulse
loop cool
43
Input 1
44
Input 2
45
Input 3
46
Input 4
47
Input 5
48
Input 6
49
Input 7
50
Input 8