beautypg.com

On/off control, Proportional control – Watlow CLS200 User Manual

Page 170

background image

Chapter 8: Tuning and Control

CLS200 Series User’s Guide

154

Watlow Anafaze

Doc.# 0600-3050-2000

On/Off Control

On/off control is the simplest way to control a process. The
controller turns an output on or off when the process vari-
able reaches limits around the desired setpoint. This limit
is adjustable; Watlow Anafaze controllers use an adjust-
able spread.

For example, if the setpoint is 1,000˚ F and the spread is
20˚ F, the heat output switches on when the process vari-
able drops below 980˚ F and off when the process rises
above 1,000˚ F. A process using on/off control cycles around
the setpoint. Figure 8.1 illustrates this example.

Figure 8.1 On/Off Control

Proportional Control

Proportional control eliminates cycling by increasing or de-
creasing the output proportionally with the process vari-
able’s deviation from the setpoint.

The magnitude of proportional response is defined by the
proportional band. Outside this band, the output is either
100% or 0%. Within the proportional band the output pow-
er is proportional to the process variable’s deviation from
the setpoint.

For example, if the setpoint is 1,000˚ F and the proportional
band is 20˚ F, the output is:

0% when the process variable is 1,000˚ F or above

50% when the process variable is 990˚ F

75% when the process variable is 985˚ F

100% when the process variable is 980˚ F or below

However, a process which uses only proportional control
settles at a point above or below the setpoint; it never
reaches the setpoint by itself. This behavior is known as off-
set
or droop.

Heat Off

Heat On

Setpoint

Setpoint - Spread

Process

On

Heat Off

Output

Off

Variable

980

°

F

1,000

°

F