Chapter 10: Linear Scaling Examples

CLS200 Series User’s Guide

190

Watlow Anafaze

Doc.# 0600-3050-2000

Table 10.1 Input Readings

The scaling values setup in the SETUP LOOP INPUT menu
are shown in Table 10.2 .

Table 10.2 Scaling Values

Process

Variable

Displayed

Sensor

Input

Reading, Percent of

Full Scale (%FS)

50.0 PSI

20 mA

100%FS

0.0 PSI

4 mA

100% x (4 mA/20 mA) = 20%FS

Parameter

Prompt

Value

High Process Variable

HIGH PV

50.0 PSI

High Sensor Reading

HIGH RDG

100.0%FS

Low Process Variable

LO PV

0.0 PSI

Low Sensor Reading

LO RDG

20.0%FS