Commands

7-71

Examples for the commands AND [ ], AND NOT [ ], OR [ ], OR NOT [ ], EXCLUSIVE OR [ ],
EXCLUSIVE OR NOT [ ].
With the use of parentheses, an instruction listing may be developed according to the following logic
block-diagram.

M500 ••

OR

M501 ••

AND

•••••

O12

I0 ••••

OR

I1 ••••

Initial state:

Marker M500 = 0Input I0 = 0

Output O12 = ?

Marker M501 = 1Input I1 = 1

Line Instruction

Accumulator Contents

Operand Contents

bit 31

7

0

... x x x x x x

x

x x x x x x x

Program-stack:

1 L M500

2 O M501

3 A [

4 L I0

5 O I1

6 ]

7 = O12

xxxxxxxx

1

xxxxxxx

bit 7

0

15

... x x x x x x

0

x x x x x x x

... x x x x x x

1

x x x x x x x

... x x x x x x

1

x x x x x x x

... x x x x x x

0

x x x x x x x

... x x x x x x

1

x x x x x x x

... x x x x x x

1

x x x x x x x

... x x x x x x

1

x x x x x x x

0

1

0

1

1

Line 1:

Marker state M500 is loaded into the Logic Accumulator.

Line 2:

The Logic Accumulator is gated with Marker M501.

Line 3:

Open parentheses: the Accumulator contents are buffered on the Program Stack.

Line 4:

Input state I0 is loaded into the Logic Accumulator.

Line 5:

The Logic Accumulator is gated with Input I1.

Line 6:

Close parentheses: Accumulator content is gated with the content of the Program Stack,
according to the command (A[, O[, NO[ ...).

Line 7:

The result of the complete logical process is assigned to Output O12.

Note:
The functional sequence is in principle the same for word execution, with the exception that the
whole Accumulator is written onto the Stack.