4 servo sensitivity (sv) – HEIDENHAIN TNC 306 Technical Manual User Manual
Page 166
4-66
TNC 406/TNC 306
4 Gap control
3/97
Example of a table created in the PLC program:
EROTAB
;first element: byte
TXT0 "POWER STAGE NUMBER"
TXT1 "LEISTUNGSSTUFE NR."
TXT2 " French dialog"
TXT3 " Italian dialog"
NAME "NR"
ELEM B,#,I1-25,1 ;byte 668 = begin of PLC-location
;
;second element: byte
TXT0 "LOW VOLTAGE CURRENT"
TXT1 "STROM BEI NIEDRIGER SPANNUNG"
TXT2 " French dialog "
TXT3 " Italian dialog "
NAME "LV"
ELEM B, ,I99,0,FRST ;669
.............
TXT0 "SERVO SENSITIVITY 1..99%"
TXT1 "SERVO EMPFINDLICHKEIT 1..99%"
TXT2 " French dialog"
TXT3 " Italian dialog "
NAME "SV"
ELEM B, ,I1-99,0,SENS ;675
.............
TXT0 "TWO-TIMES GAP [MM/INCH]"
TXT1 "DIAMETRALER SPALT [MM/INCH]"
TXT2 " French dialog"
TXT3 " Italian dialog"
NAME "2G "
ELEM W,#,R3D9I,0,Q201,Q155 ;692
..............
ENDTAB
4.7.4 Servo sensitivity (SV)
The eroding parameter Servo Sensitivity SV in the erosion table is evaluated directly by the control.
Its function is to adjust the gap control characteristic and thus the reaction speed to the gap signal.
SV is expressed as a percentage (0–99%) of the original characteristic gradients.
0
U
gap
[V]
F
[mm/min]
5
2.5
SV = 99
SV = 60