1.3

Test functions for the PLC-program

1.3.1 TRACE function

The TRACE function makes it possible to check the logical states of the markers, inputs, outputs,
timers and counters.

If this function is selected, the following menu appears:

TNC 406

TNC 306

SELECT I/O/C/T/M
DISPLAY TRACE BUFFER
START TRACE
END TRACE

SELECT I/O/C/T/M

Those inputs (I), outputs (O), counters (C), timers (T) or markers (M) whose logical states are to be
checked can be entered into a table in the SELECT I/O/C/T/M function. A maximum of 16 markers,
timers etc. can be simultaneously verified. Each position is interrogated via dialog. Erroneous entries
can be deleted by pressing DEL.
The memory for the trace mode (TRACE BUFFER) has space for 1024 individual states per operand,
i.e. 1024 PLC processes are recorded. In order to record the required time duration of the user, a
TRIGGER condition can be entered for each operand:

"1" = Recording when operand is logically "1"
"0" = Recording when operand is logically "0"

If the trigger position is verified with the NOENT key, it means that a trigger condition is not
required. 512 states are recorded before and after a trigger event. The trigger event is regarded as
fulfilled only when the conditions for all operands are simultaneously fulfilled with TRIGGER.

Example:

M2618 1
M2780 0
M2781 1
I5
Trigger event:

M2618 logical "1"
M2780 logical "0"
M2781 logical "1"

The state of I5 has no significance for the trigger event: it is, however, recorded.

If no trigger condition is entered for the operands, the states of the operands are continually
recorded and, after ending the trace mode, the last 1024 states are displayed.
To exit the SELECT I/O/C/T/M function, press END.