Connecting Your Ultra1500

3-11

To wire your input power:

1. Prepare your wires by stripping approximately 8 mm (0.33 in.) of

insulation from the end.

Ferrules 2mm (0.79 in.) in diameter may be attached to the wires at this
point. Ferrules ensure that wires strands are not inadvertently exposed.

Note: The Ultra1500 motor power cables listed in Appendix C for use with

the TL-Series motors have ferrules, and do not require stripping.

2. Route the power cable to your Ultra1500 drive.

3. Locate the six-position Input Power terminal block and remove the plastic

connector. Refer to Understanding Ultra1500 Connectors in Chapter 2 for the
front panel connections of your Ultra1500 drive.

4. Using the connector tool provided with the drive (Wago 231-131 shown in

Figure 3.9), open the clamp for each of the terminal locations and insert
wires as shown in the table below.

IMPORTANT

The AC input power lines (L1, L2, L3, L1C, and L2C)
require dual element time delay (slow acting) fuses to
accommodate inrush current. Refer to the section
Ultra1500 Power Specifications in Appendix A for the inrush
current on the AC power inputs, as well as fuse
recommendations.

IMPORTANT

Use caution not to nick, cut, or otherwise damage
strands as you remove the insulation.

If you have this drive:

Insert this wire from the power
supply:

Into this terminal on Input Power
Connector:

2092-DA1,

2092-DA2, or

2092-DA3

L1 (main AC)

L1

L2 (main AC)

L2

Ground (main AC)

2092-DA1 and -DA2 on side of heatsink

2092-DA3 on front of heatsink

L1C (control AC)

L1C

L2C (control AC)

L2C

2092-DA4 or

2092-DA5

L1 (main AC)

L1

L2 (main AC)

L2

L3 (main AC)

L3

Ground (main AC)

2092-DA4 and -DA5 on front of heatsink

L1C (control AC)

L1C

L2C (control AC)

L2C