Determining Your Type of
Input Power

Before you wire your Ultra1500 system you must determine the type of input
power you are connecting to. The Ultra1500 is designed to operate only in
grounded environments.

Grounded Power Configuration

The grounded power configuration allows you to ground your single-phase or
three-phase power at a neutral point. Match your secondary to one of the
examples below and be certain to include the grounded neutral connection.

Figure 3.1
Three-Phase Power Configuration (WYE Secondary)

Figure 3.2
Three-Phase Grounded Power Configuration (Delta Secondary)

L1

L2

L3

Bonded cabinet

ground bus

Transformer (WYE) Secondary

Ground grid or

power distribution ground

Ultra1500 Three-Phase AC Input
2092-DA4 and -DA5

L1, L2, and L3 Terminals

L1

L2

L3

L1

L3

L2

Transformer (Delta) Secondary

Ground Grid or Power Distribution Ground

Ultra1500 Three-Phase AC Input
2092-DA4 and -DA5

L1, L2, and L3 Terminals

Bonded Cabinet Ground Bus

Transformer (Delta) Secondary

Ultra1500 Three-Phase AC Input

2092-DA4 and -DA5

L1, L2, and L3 Terminals