This table defines only those variables that can be selected for the
following parameters:
Pr-5.12 Analog Output 1: Signal on page D-28,
Pr-5.13 Analog Output 2: Signal on page D-28,
Pr-6.07 Fault Detail Setup: Channel A on page D-30
Pr-6.08 Fault Detail Setup: Channel B on page D-30,
Pr-6.09 Fault Detail Setup: Channel C on page D-30, and
Pr-6.10 Fault Detail Setup: Channel D on page D-31.
16
Error History
Up to eight alarms stored in numerical order (most
recent =1, to oldest =8) with error code number:
Most significant digit is alarm number (1–8),
Least significant six digits are the error code number
referenced in the Error Displays beginning on page 6-5.
e.g., 1-E004 = most recent error is a Motor Overtemp
17
Firmware Version
e.g., vErx.yy where x = version, yy = revision
18
Motor Temperature
%
19
Instantaneous Output
Power
Watts
20
Output Power Limit
Ratio
%
Variable
Numbers
Name
Unit
00
Velocity Feedback
rpm or mm/sec
01
Velocity Command
rpm or mm/sec
02
Velocity Error
rpm or mm/sec
03
Current Command
0.1% of motor rated continuous torque
04
Follower Position
counts
05
Master Position
counts
06
Position Error
counts
07
Position Command
Count Frequency
0.1 kilocounts/sec
08
Commutation Angle
0.1
o
(degrees)
09
Mechanical Angle
0.1
o
(degrees)
10
Shunt Power Limit Ratio
%
11
Bus Voltage
V
12
Absolute Rotations
revolutions
13
Velocity Command
Offset
mV
14
Current Command Offset mV
Variable
Numbers
Name
Unit