Publication 2092-UM001D-EN-P — July 2005

Connecting Your Ultra1500

3-7

Figure 3.6
Motor Power Cable Shield Connection

Safety Precautions

Observe the following safety precautions when wiring your Ultra1500 drive.

U

V

W

P2

2092-DA1 or -DA2

Side View

Ground Terminal Screw

Shielded
Power
Cable

2092-DA3

Front View

Ground Terminal Screws

Shielded
Power
Cable

Note: Ground terminal
arrangement of the
2092-DA4 and 2092-DA5
drives. is shown in Figure
3.5
on page 3-6.

ATTENTION

!

DC bus capacitors may retain hazardous voltages after
input power has been removed. Before working on the
drive, measure the DC bus voltage to verify it has reached a
safe level or wait the full time interval listed on the drive
warning label. Failure to observe this precaution could
result in severe bodily injury or loss of life.

Do not attempt to defeat or override the drive fault circuits.
You must determine the cause of a fault and correct it
before you attempt to operate the system. If you do not
correct a drive or system malfunction, it could result in
personal injury and/or damage to the equipment as a result
of uncontrolled machine system operation.

Test equipment (such as an oscilloscope or chart recorder)
must be properly grounded. Failure to include an earth
ground connection could result in a potentially fatal voltage
on the oscilloscope chassis.