Installing Your Ultra1500

Ventilation Requirements

This section provides information to assist you in sizing your cabinet and
locating your Ultra1500 drive(s) inside the cabinet.

Figure 1.2
Minimum Clearance Requirements

Refer to Appendix A for Ultra1500 power dissipation specifications.

50.0 mm (1.97 in.) clearance

for airflow and installation

50.0 mm (1.97 in.) clearance

for airflow and installation

Allow 10.0 mm (0.39 in.)

between drives

Minimum cabinet depth:
2092-DA1, -DA2, and -DA3 = 216 mm (8.52 in.)
2092-DA4, and -DA5 = 261 mm (10.28 in.)

Do not mount drive on its side.

Ultra1500s mounted

vertically on the panel

Allow 30.0 mm (1.18 in.)

from adjacent wall

IMPORTANT

If the cabinet is ventilated, use filtered or conditioned air to
prevent the accumulation of dust and dirt on electronic
components. The air should be free of oil, corrosives, or
electrically conductive contaminates.