Ultra1500 Operator Interface

D-27

Pr-5.07 Brake Active Delay

Pr-5.08 Stopping Functions: Braking Application Speed

Pr-5.09 Following Error Limit

Pr-5.10 AC Line Loss Fault Delay

Units:

10 msec

Applicable Operating Mode:

All

Ultraware Link:

Stopping Functions: Disable Delay

Description:

Brake Active Delay is the time from when Drive Disable
command is received to when the brake starts operating.

Range:

0 to 1000

Default:

50

Units:

10 msec

Applicable Operating Mode:

All

Ultraware Link:

Brake Active Delay

Description:

Braking Application Speed is the feedback speed, after
disabling the drive, below which the motor brake is engaged.

Range:

0 to 1000

Default:

100

Units:

rpm for rotary motors

mm/sec for linear motors

Applicable Operating Mode:

All

Ultraware Name:

Braking Application Speed

Description:

A Follower Error fault occurs when the difference between
position command and actual position is greater than value
set by the Following Error Limit parameter.

Range:

0 to 99999

Default:

20480

Units:

Counts

Applicable Operating Mode:

Follower

Ultraware Link:

Following Error Limit

Description:

AC Line Loss Fault Delay is the time allowed for power to be
down without triggering of a power down fault.

Range:

20 to 1000

Default:

20

Description:

Disable Delay is the time from when Drive Disable command
is received to when the command is actually executed.

Range:

0 to 1000