Publication 2092-UM001D-EN-P — July 2005

5-32

Ultra1500 Application Examples

Figure 5.13
Velocity Regulator Step Response with Varying Integrator Time

Integrator Mode

The Integrator Mode parameter controls how the integral term is applied to
the velocity regulator. It can be set to Always On, High Current Disable,
Velocity Command Disable, or Position Error Disable. This parameter
introduces a nonlinear control to the integrator (preventing it from integrating
in certain conditions) that may be useful in reducing or eliminating overshoot
in the velocity response from integrator windup. Integrator windup occurs
when the current regulator is saturated but the velocity error is not eliminated,
and usually causes overshoot during command changes

Velocity
Command

I = 0

I = 100

I = 10

I = 1

Integrator Time = 0

Integrator Time = 1

Time (msec)

0

20

40

60

80

0

50

100

150

200

450

400

350

300

250

V

elocity

Integrator Time = 100