beautypg.com

Controllogix 1756-m02ae system connections – Rockwell Automation 2092-DAx Ultra1500 User Manual User Manual

Page 148

background image

Publication 2092-UM001D-EN-P — July 2005

B-4

Interconnect and Cable Diagrams

ControlLogix 1756-M02AE
System Connections

Figure B.3 shows the recommended connections for a typical 1756-M02AE
system using an Allen-Bradley ControlLogix PLC control system.

Figure B.3
Ultra1500 to 1756-M02AE System Interface Diagram

1756-M02AE

+OUT

-OUT

+ENABLE

NOTES:

1.

IN THIS EXAMPLE, THE 1756-M02AE PROVIDES A CURRENT COMMAND TO THE DRIVE AND CLOSES THE VELOCITY LOOP. IF THE
APPLICATION REQUIRES THE DRIVE TO CLOSE THE VELOCITY LOOP, THE VELOCITY COMMAND OF THE 1756-M02AE SHOULD BE
CONNECTED TO THE ANALOG VELOCITY COMMAND INPUT OF THE DRIVE INSTEAD, FOUND ON PINS 19 AND 20.

2.

INPUT1 MUST BE CONFIGURED TO HAVE ENABLE FUNCTIONALITY USING ULTRAWARE.

3.

OUTPUT2 MUST BE CONFIGURED TO HAVE DRIVE READY FUNCTIONALITY USING ULTRAWARE.

ULTRA1500

1

-ENABLE

DRVFLT+

IN_COM

24V

POWER

SUPPLY

ICMD+

ICMD-

INPUT1

24V IN

OUTPUT2-

OUTPUT2+

21

22

3

1

44

43

CHASSIS

SHIELD

CN1

+CHA

-CHA

AM+

AM-

29

30

+CHB

-CHB

BM+

BM-

31

32

+CHZ

-CHZ

IM+

IM-

33

34

+

-

2

3