Ultra1500 Connector Data

2-9

Figure 2.4
Transistor Output Hardware Configuration for OUTPUT 1, OUTPUT 2, OUTPUT 3, and
FAULT Signals

Figure 2.5
Transistor Output Hardware Configuration for FAULT1, FAULT2, and FAULT3 Signals

The following table provides a description of the digital output specifications.

Parameter

Description

Minimum

Maximum

ON State
Current

Current flow when the output transistor is ON

20 mA

OFF State
Current

Current flow when the output transistor is OFF

0.1 mA

ON State
Voltage

Voltage across the output transistor when ON

1.2V

OFF State
Voltage

Voltage across the output transistor when OFF

28V

OUTPUT1-

TLP127

330

OUTPUT1+

0.5A Fuse

Logic Power

Ultra1500

Drive

Logic Ground

FAULT 1

KRC105S

Ultra1500 Drive