2-6

Ultra1500 Connector Data

The following table provides a description of the digital input specifications.

Figure 2.3 depicts common interface types for Ultra1500 Digital Inputs.

Parameter

Description Minimum

Typical

Maximum

ON State Voltage

Voltage applied to the input, with respect to
I/O common, to guarantee an ON state.

2V

ON State Current

Current flow to guarantee an ON State

6.9 mA

OFF State Voltage

Voltage applied to the input, with respect to
the positive terminal of the 24V power
supply, to guarantee an OFF state.

-1 V

Firmware Scan
Delay

Signal delay from the digital input to the
firmware-accessible registers.