Connecting Your Ultra1500

Figure 3.5
Chassis Ground Configuration (Multiple Ultra1500 Systems on One Panel)

Motor Power Cable Shield Termination

Factory supplied motor power cables for TL-Series motors are shielded, and
the power cable is designed to be terminated at the drive during installation. A
separate lugged ground wire connects to the shield braid. The lugged wire
must be connected to the ground terminal on the drive’s heatsink (refer to
Figure 3.6 for location).

U

V

W

P1

P2

B1

B2

L1

L2

L2C

N

L3

L1C

CN3

CN2

BATT

CN1

U

V

W

P1

P2

B1

B2

L1

L2

L2C

N

L3

L1C

CN3

CN2

BATT

CN1

Bonded ground bar

(optional)

Bonded cabinet

ground bus

Ground grid or power

distribution ground

Always follow NEC and applicable local codes

Chassis ground

Chassis ground

Chassis ground

Chassis ground

2092-DA1 or -DA2

2092-DA1 or -DA2

2092-DA3

2092-DA4 or -DA5

Note: Refer to Figure 3.6 on page 3-7 for

ground terminal location on the 2092-DA1 heatsink.

ATTENTION

!

To avoid hazard of electrical shock, ensure shielded power
cables are grounded at a minimum of one point for safety.