Fuse and contactor specifications, Power dissipation specifications, To fuse and contactor specifications in – Rockwell Automation 2092-DAx Ultra1500 User Manual User Manual
Page 138: Fuse and contactor, Specifications, Ge a-4
Publication 2092-UM001D-EN-P — July 2005
A-4
Specifications and Dimensions
Fuse and Contactor Specifications
Use class CC, J, or R class fuses, with current ratings as indicated in the table
below. The table below lists fuse examples recommended for use with the
Ultra1500 drives.
Refer to Power Wiring Requirements in Chapter 3 for input wire size.
1 For contactors,
x
represents coil voltage, and
y
represents number of contacts.
Power Dissipation Specifications
Use the following table to size an enclosure and calculate required ventilation
for the Ultra1500. Typical heat losses run approximately one-half maximum
power losses. The maximum power losses are shown below.
Catalog Number
Input Type
Input
Voltage
Recommended Bussmann
®
Fuse
Recommended
Allen-Bradley
Contactor
1
Class CC
Class J
Class RK5
2092-DA1
Main Input Power
230V, 1
φ
FNQ-R-7
N/A
N/A
100-M05Nxy
2092-DA2
100-M09Nxy
2092-DA3
FNQ-R-10 100-M12Nxy
2092-DA4
230V, 3
φ
FNQ-R-15 LPJ-15
100-C16xy
2092-DA5
FNQ-R-20 LPJ-20
100-C23xy
2092-DA1, 2092-DA2,
2092-DA3, 2092-DA4,
and 2092-DA5
Control Input Power 230V, 1
φ
FNQ-R-7-1/2 LPJ-6
FRS-R-2-1/2
N/A
Catalog Number
Maximum Loss
Watts
2092-DA1
50
2092-DA2
50
2092-DA3
50 + dissipative shunt
2092-DA4
100 + dissipative shunt
2092-DA5
150 + dissipative shunt