beautypg.com

Fuse and contactor specifications, Power dissipation specifications, To fuse and contactor specifications in – Rockwell Automation 2092-DAx Ultra1500 User Manual User Manual

Page 138: Fuse and contactor, Specifications, Ge a-4

background image

Publication 2092-UM001D-EN-P — July 2005

A-4

Specifications and Dimensions

Fuse and Contactor Specifications

Use class CC, J, or R class fuses, with current ratings as indicated in the table
below. The table below lists fuse examples recommended for use with the
Ultra1500 drives.

Refer to Power Wiring Requirements in Chapter 3 for input wire size.

1 For contactors,

x

represents coil voltage, and

y

represents number of contacts.

Power Dissipation Specifications

Use the following table to size an enclosure and calculate required ventilation
for the Ultra1500. Typical heat losses run approximately one-half maximum
power losses. The maximum power losses are shown below.

Catalog Number

Input Type

Input
Voltage

Recommended Bussmann

®

Fuse

Recommended
Allen-Bradley
Contactor

1

Class CC

Class J

Class RK5

2092-DA1

Main Input Power

230V, 1

φ

FNQ-R-7

N/A

N/A

100-M05Nxy

2092-DA2

100-M09Nxy

2092-DA3

FNQ-R-10 100-M12Nxy

2092-DA4

230V, 3

φ

FNQ-R-15 LPJ-15

100-C16xy

2092-DA5

FNQ-R-20 LPJ-20

100-C23xy

2092-DA1, 2092-DA2,
2092-DA3, 2092-DA4,
and 2092-DA5

Control Input Power 230V, 1

φ

FNQ-R-7-1/2 LPJ-6

FRS-R-2-1/2

N/A

Catalog Number

Maximum Loss
Watts

2092-DA1

50

2092-DA2

50

2092-DA3

50 + dissipative shunt

2092-DA4

100 + dissipative shunt

2092-DA5

150 + dissipative shunt