Basic setting

Two display modes are possible. The hatched mode is recommended
for print-out on black-and-white printers or displays (e.g. laptop). In
all other cases, the colour setting should be used.

Language

The engineering tool language can be selected.

Comparison (F3)

Permits comparison of the active engineering with the contents of the connected KS 98-1 or of the simulation. The
operation is started immediately after clicking on this item. The comparison result is displayed in a message window.
Possible messages are shown in Fig.: 74 to Fig.: 76. (close window with key “x”).

Debug (F4)

Activates cyclic display of signals in the additionally created monitor blocks
(see also chapter 3.5).

Deleting display functions

As display functions are not transmitted to KS 98-1, deleting all these functions at the end of the debug phase may
make sense.

Trend

See description of ‘Universal trend function’ (chapter 3.6 from page 72 )

Set status “pwrchk”

The STATUS function provides a digital output “pwrchk” (power fail check), which goes to “0" when the power returns
after a failure.

By means of the function “Set status pwrchk” this output can be reset to “1", thus enabling a functional test of the en -
gineering to be triggered after a power failure.