I-9.4 calibration 35, I-9.5 online/offline 35, Calibration 35 – West Control Solutions KS98-1 User Manual
Page 35: Online/offline 35, I-9.4 calibration, I-9.5 online/offline

I-9.4
Calibration
Press ID to select the input and M to open the calibration page.
Transducer input:
Adjusting the transducer start and end:
Ü
Select
Quit Set transducer to start
*
Press
M r Quit blinks
Ö
Press I r
Set 0% blinks
ä
Wait until the input has settled (min. 6 s)
#
Press M r
0% done is displayed
<
Set transducer to end
>
Press M r
0% done blinks
y
Press I 3x r
Set 100% blinks
x
Wait until the input has settled
c
Press M r
100% done is displayed.
Calibration is finished. For exit from calibration press D until nothing is marked and then press M.
Two resistance thermometers:
Calibration of lead resistance effect
Ü
Select
Quit .
Short-circuit both thermometers in the connecting head
*
Press
M r Quit blinks
Ö
Press I r
Set Dif blinks
ä
Wait until the input has settled (min. 6 s)
#
Press M r
Cal done is displayed
Lead resistance adjustment is finished. Remove both short cir-
cuits. For exit from calibration press D until nothing is marked
and then press M.
I-9.5
Online/Offline
For configuration changing, switch the unit to ‘Offline’ and back to ‘Online’ after alteration.
a
When switching the unit to status off-line, the outputs will remain in the status at switch-over time !!!
+
By switching over to on-line, all data is saved.
+
When terminating the off-line mode by cancellation (Escape config.) the data saved last is loaded back into the wor -
king memory.
9499-040-82711
Instrument settings in the main menu
Calibration
I-35
Transducer
Temp. difference