Iii-4.4 bounce (debouncer (no. 63)) 108, Iii-4.5 exor (exclusive or gate (no. 64)) 108, Bounce 108 – West Control Solutions KS98-1 User Manual
Page 108: Debouncer 108, Exclusive or gate 108, Exor 108, Iii-4.4 bounce (debouncer (no. 63))
III-4.4
BOUNCE (debouncer (No. 63))
This function is used for de-bouncing a logic signal. The change of input signal
d1 is transferred to output z1 only,
when it remained constant for the time adjusted in parameter Delay. The time-out accuracy is dependent of the sam -
pling interval assigned to the function.
Example:
–
Delay = 0,5s for assignment to
- sampling interval 100ms means that the signal is transferred only after ? 0,5s.
- Sampling interval 200ms means that the signal is transferred only after ? 0,6s.
- Sampling interval 400ms means that the signal is transferred only after ? 0,8s.
- Sampling interval 800ms means that the signal is transferred only after ? 0,8s.
Parameter
Description
Range
Default
Delay
Switch-on and off delay time
0...999 999 [s]
0
III-4.5
EXOR (exclusive OR gate (No. 64))
z
d EXOR d
1
1
2
=
Logic inputs
d1 and d2 are combined into z1 according to the truth table given below. Unused inputs are inter-
preted as logic 0.
Output
z1 is 0, when the two inputs are equal (both 0 or both 1).
d1
d2
z1
not z1
0
0
0
1
0
1
1
0
1
0
1
0
1
1
0
1
9499-040-82711
Logic functions
BOUNCE (debouncer (No. 63))
III-108
d1
z1
Delay
Delay Delay
d1
d2
=1
z1
not z1