beautypg.com

I-3 technical data 12, Technical data 12 - 17, I-3 technical data – West Control Solutions KS98-1 User Manual

Page 12: General, Environmental conditions

background image

I-3

Technical data

General

Housing

Plug-in module, inserted from front.

Material: Makrolon 9415, flame-retardant, self-extinguishing

Flammability class: UL 94 VO

Front-panel / display

160 x 80-dot LCD matrix display

4 LEDs, 4 foil-covered keys

Front interface port (

standard)

Front-panel socket for PC adapter
(see „Accessories“ page 19).

Protection mode

(to EN 60 529, DINVDE 0470)

Front: IP 65

Housing: IP 20

Terminals: IP 00

Safety tests

Complies with EN 61 010-1

w

Overvoltage category: III

w

Contamination class: 2

w

Working voltage range: 300 VAC

w

Protection class: I

DIN EN 14597

The device may be used as temperature control and limiting equip-
ment according to DIN EN 14597.

CE marking

Meets the EuropeanDirectives regarding „Electromagnetic Compa-
tibility“ and „Low-voltage equipment“(r page 23)

The unit meets the following European guidelines:

q

Electromagnetic compatibility (EMC): 89/336/EEC
(as amended by 93/97/EEC)

q

Electrical apparatus (low-voltage guideline):
73/23/EEC (as amended by 93/68/EEC).

Evidence of conformity is provided by compliance with EN 61326-1
and EN 61010-1

cULus certification

cULus-certification
(Type 1, indoor use) File: E 208286

a

RC protective circuitry must be fitted with inducti-
ve load !

Electrical connections

Screw terminals for conductor cross-section from 0,5 - 2,5 mm

2

Mounting method

Panel mounting with 4 fixing clamps at top/bottom

Mounting position

Not critical

Weight

Approx. 0.75 kg with all options

Environmental conditions

Permissible temperatures

For operation: 0...55°C

For specified accuracy: 0...60°C, optionC

For UL-Devices: Operation and protected operation 0...50°C

Storage and transport: –20...60 °C
Temperature effect:

£ 0.15% / 10 K

Climatic category

KUF to DIN 40 040

Relative humidity:

£ 75% yearly average, no condensation

Shock and vibration

Vibration test Fc: To DIN 68-2-6 (10...150 Hz)

Unit in operation: 1g or 0.075 mm,

Unit not in operation: 2g or 0.15 mm

Shock test Ea:To DIN IEC 68-2-27 (15g, 11 ms)

Technical data

9499-040-82711

I-12