General
Housing
Plug-in module, inserted from front.
Material: Makrolon 9415, flame-retardant, self-extinguishing
Flammability class: UL 94 VO
Front-panel / display
160 x 80-dot LCD matrix display
4 LEDs, 4 foil-covered keys
Front interface port (
standard)
Front-panel socket for PC adapter
(see „Accessories“ page 19).
Protection mode
(to EN 60 529, DINVDE 0470)
Front: IP 65
Housing: IP 20
Terminals: IP 00
Safety tests
Complies with EN 61 010-1
w
Overvoltage category: III
w
Contamination class: 2
w
Working voltage range: 300 VAC
w
Protection class: I
DIN EN 14597
The device may be used as temperature control and limiting equip-
ment according to DIN EN 14597.
CE marking
Meets the EuropeanDirectives regarding „Electromagnetic Compa-
tibility“ and „Low-voltage equipment“(r page 23)
The unit meets the following European guidelines:
q
Electromagnetic compatibility (EMC): 89/336/EEC
(as amended by 93/97/EEC)
q
Electrical apparatus (low-voltage guideline):
73/23/EEC (as amended by 93/68/EEC).
Evidence of conformity is provided by compliance with EN 61326-1
and EN 61010-1
cULus certification
cULus-certification
(Type 1, indoor use) File: E 208286
a
RC protective circuitry must be fitted with inducti-
ve load !
Electrical connections
Screw terminals for conductor cross-section from 0,5 - 2,5 mm
2
Mounting method
Panel mounting with 4 fixing clamps at top/bottom
Mounting position
Not critical
Weight
Approx. 0.75 kg with all options
Environmental conditions
Permissible temperatures
For operation: 0...55°C
For specified accuracy: 0...60°C, optionC
For UL-Devices: Operation and protected operation 0...50°C
Storage and transport: –20...60 °C
Temperature effect:
£ 0.15% / 10 K
Climatic category
KUF to DIN 40 040
Relative humidity:
£ 75% yearly average, no condensation
Shock and vibration
Vibration test Fc: To DIN 68-2-6 (10...150 Hz)
Unit in operation: 1g or 0.075 mm,
Unit not in operation: 2g or 0.15 mm
Shock test Ea:To DIN IEC 68-2-27 (15g, 11 ms)
Technical data