Analog outputs:
Inp_a
measured value channel a
Inp_b
measured value channel b
Parameter
Description
Value
Default
x1a in
Measured value correction Inp_a, P1 input value
Real
0
x1aOut
Measured value correction Inp_a, P1 output value
0
x2a in
Measured value correction Inp_a, P2 input value
100
x2aOut
Measured value correction Inp_a, P2 output value
100
x1b in
Measured value correction Inp_b, P1 input value
0
x1bOut
Measured value correction Inp_b, P1 output value
0
x2b in
Measured value correction Inp_b, P2 input value
100
x2bOut
Measured value correction Inp_b, P2 output value
100
Configuration
Description
Value
Default
Typ_a
Typ_b
Pt100 (850) -200 ... 850 °C
00
0
Pt100 (100) -200 ... 100 °C
01
Pt1000 (-1) -200 ... 850 °C
02
Pt1000 (-2) -200 ... 100 °C
03
Ni100 -60 ... 180 °C
04
Ni1000 -60 ... 180 °C
05
R160 resistance 0 ... 160 Ohm
06
R450 resistance 0 ... 450 Ohm
07
R1600 resistance 0 ... 1600 Ohm
08
R4500 resistance 0 ... 4500 Ohm
09
Potentiometer 160 Potentiometer 0 ... 160 Ohm
10
Potentiometer 450 Potentiometer 0 ... 450 Ohm
11
Potentiometer 1600 Potentiometer 0 ... 1600 Ohm
12
Potentiometer 4500 Potentiometer 0 ... 4500 Ohm
13
Fail_a
Fail_b
Switched off
0
1
Upscale, Inp_a (Inp_b) = x100_a (x100_b)
1
Downscale, Inp_a (Inp_b) = x0_a (x0_b)
2
Substitute value, Inp_a (Inp_b) = XaFail (XbFail)
3
Xakorr
Xbkorr
Measured value correction Inp_a (b) switched off
0
0
Measured value correction Inp_a (b) effective
1
Unit_a
Unit_b
Unit of the measured value of Inp_a (b) = °C
1
1
Unit of the measured value of Inp_a (b) = °F
2
Mode
Inp_a and Inp_b: 2-wire connection
0
0
Inp_a: 3-wire connection no Inp_b
1
Inp_a: 4-wire connection no Inp_b
2
x0_a(b)
Physical value Inp_a (Inp_b) at 0%
Real
0
x100_a(b)
Physical value Inp_a (Inp_b) at 100%
Real
100
Xa(b)Fail
Substitute value with sensor error at Inp_a(b)
Real
0
Tfm_a(b)
Filter time constant of _a (Inp_b) in seconds
Real
0,5
Kal_1a(b)
1st calibration value Inp_a(b) (read only)
Real
0
Kal_2a(b)
2nd calibration value Inp_a(b) (read only)
Real
100