Configuration data CONTR, CONTR+

Configuration Description

Values

Default

CFunc

Control

behaviour:

Signaller 1 output

Signal 1

Signaller 2 outputs

Signal 2

2-point controller

2-point

3-point controller (heating/cooling switching)

3-point

3-point controller (heat.continuous/cool.switching)

Cont/swi

3-point controller (heat.switching/cool.continuous)

Swi/Cont

triangle-star-off (d/Y-off)

2P-DSO

3-point stepping controller

Stepping

3-point-stepping controller with pos. feedback Yp

Step+Yp

Continuous controller

Cont

t

Continuous controller with split-range operation

splitRang

Continuous controller with position feedback Yp

Cont Yp

CType

Controller type

Standard controller r page

Standard

t

Ratio controller r page

Ratio

3-element controller r page 267

3-elem

WFunc

function

control r page

t

/cascade control r page

Sp/casc

CMode

Output action

Inverse output action

Inverse

t

Direct output action

Direct

CDiff

Differentiation

Xw differentiation

Xw

t

X differentiation

X

CFail

Behaviour with

sensor error

Neutral

Neutral

Ypid = Ymin (0%)

Ymin

t

Ypid = Ymax (100%)

Ymax

Ypid = Y2 (no adjustment via front panel)

Y2

Ypid = Y2 (automatic) or Yman (manual operation)

Y2/Yman

COVC

Output limiting

No override control

Off

t

Override control +

OVC+

Override control -

OVC-

Override control + / -

OVC+/OVC-

WTrac

Int. tracking

No tracking of Wint

Off

t

tracking

SP-track

Process value tracking

PV-track

Ratio

Ratio

controller

function:

(x1 + N0) / x2 r page 2667

Type 1

t

(x1 + N0) / (x1 + x2) r page 266

Type 2

(x2 -x1 + N0) / x2 r page 266

Type 3

XDp

Digits behind the decimal point (process value)

0...3

0

Disp

Contents of

bargraph line:

Output variable

Y

t

Control deviation

XW

Xeff

Xeff

OMode

Self-tuning mode:

Standard

t

OCond

Condition for

process at

rest:

grad = 0

grad=0

t

grad <0 (controller inverse) grad >0 (controller direct)

grad<0/>0

grad <>0

grad<>0

Xn0

Span start

-29999 ... 999 999

0

Xn100

Span end

-29999 ... 999 999

100

SFac

Factor stoichiom. ratio

0,01 ... 99,99

1,00

9499-040-82711

Controller

Parameter and Konfiguration for CONTR, CONTR+