beautypg.com

Iii-6.2 inte (integrator (no. 51)) 126, Inte 126, Integrator 126 – West Control Solutions KS98-1 User Manual

Page 126: Iii-6.2 inte (integrator (no. 51))

background image

III-6.2

INTE (integrator (No. 51))

The integrator forms the integral according to equation:

( )

(

)

( )

[

]

y t

y t

t

t

T

x t

x

s

s

1

1

1

0

=

-

+ ×

+

ts

sampling interval

x1(t)

instantaneous x1

T

Integration constant

y1(t)

y1 after t=n*ts

n

Number of calculation cycles

y1(t-ts)

previous y1

x0

Input offset

The complex transfer function is:

( )

F p

T p

=

×

1

Unused control inputs are interpreted as logic “0". With simultaneous input of several control commands:

reset

= 1 has priority over preset and stop

preset

= 1 priority over stop

Integrator output

y1 is limited to the preset limits (Min, Max): Min ß y1 ß Max. When exceeding Min or

Max, the integrator is stopped automatically and the relevant control output min or max is set to logic 1. Limit value
monitoring uses a fixed hysteresis of 1 % referred to operating range (

Max - Min)

Inputs/outputs

Digital inputs
stop

= 1 The integrator is stopped for the duration of the stop command. Output y1 does not change.

reset

= 1 The integration result is adjusted to lower limit (Min). After cancelation of

reset,

integration starts at lower limiting.

preset

= 1 The integration result is set either to a preset value y0 ( Mode=0) or to a preset variable

Preset (Mode= 1). After cancelation of the preset command, integration starts with
the actually effective preset value.

9499-040-82711

Time functions

INTE (integrator (No. 51))

III-126

preset
reset

stop

x1

z1
z2
y1

y0

Mode

?1

T

ò

MAX

MIN

MAX
MIN

Min
Max

x0

Preset