Iii-6.2 inte (integrator (no. 51)) 126, Inte 126, Integrator 126 – West Control Solutions KS98-1 User Manual
Page 126: Iii-6.2 inte (integrator (no. 51))
III-6.2
INTE (integrator (No. 51))
The integrator forms the integral according to equation:
( )
(
)
( )
[
]
y t
y t
t
t
T
x t
x
s
s
1
1
1
0
=
-
+ ×
+
ts
sampling interval
x1(t)
instantaneous x1
T
Integration constant
y1(t)
y1 after t=n*ts
n
Number of calculation cycles
y1(t-ts)
previous y1
x0
Input offset
The complex transfer function is:
( )
F p
T p
=
×
1
Unused control inputs are interpreted as logic “0". With simultaneous input of several control commands:
reset
= 1 has priority over preset and stop
preset
= 1 priority over stop
Integrator output
y1 is limited to the preset limits (Min, Max): Min ß y1 ß Max. When exceeding Min or
Max, the integrator is stopped automatically and the relevant control output min or max is set to logic 1. Limit value
monitoring uses a fixed hysteresis of 1 % referred to operating range (
Max - Min)
Inputs/outputs
Digital inputs
stop
= 1 The integrator is stopped for the duration of the stop command. Output y1 does not change.
reset
= 1 The integration result is adjusted to lower limit (Min). After cancelation of
reset,
integration starts at lower limiting.
preset
= 1 The integration result is set either to a preset value y0 ( Mode=0) or to a preset variable
Preset (Mode= 1). After cancelation of the preset command, integration starts with
the actually effective preset value.
9499-040-82711
Time functions
INTE (integrator (No. 51))
III-126
preset
reset
stop
x1
z1
z2
y1
y0
Mode
?1
T
ò
MAX
MIN
MAX
MIN
Min
Max
x0
Preset