Page 135: Inputs/outputs

III-7.2
PEAK ( peak value memory (No. 31))
Maximum input value x
max
and minimum input value x
min
are determined, stored and output at
Max and Min. With
the stop input set to 1, the extreme values determined last remain unchanged.
If the
reset input is set to 1, the extreme value memory and any applied stop command are cancelled. (x
max
and x
min
are set to the instantaneous x1 value and follow input x1, until the
reset input returns to 0.)
Unused inputs are interpreted as 0 or logic 0.
The function has a ‘memory’. This means: after power-on, it continues operating with the Min- and Max values which
existed at power-off, provided that the RAM data are still unchanged.
No parameters!
Inputs/outputs
Digital inputs
stop
With the stop input set to 1, instantaneous values Max and Min are unchanged.
reset
The reset input deletes the
Min and Max values.
Analog inputs
x1
Process value, the min and max values of which are output.
Analog outputs
Max
Maximum value
Min
Minimum value
Selecting and storage
9499-040-82711
III-135
PEAK ( peak value memory (No. 31))
Max
Min
x1
xmax
xmin
&
x x>y stop
reset